What equipment does an LEV tester use?
HSG258 paragraphs 295 and 337 list equipment for examining local exhaust ventilation (LEV). BOHS P601 sections 2.4.2 and 2.4.3 teach these methods.
- Anemometers and Pitot tubes measure air movement.
- Manometers measure pressure.
- Smoke and a dust lamp help show air movement and contaminant clouds.
- Tachometers and power meters provide fan measurements. Some examinations also use air sampling equipment.
The instruments and their uses
HSG258 paragraphs 289 to 295 describe the equipment and its limits. Choose an instrument to see what it does.
| Instrument | What it measures or shows | Where it is used | Limits the sources name |
|---|---|---|---|
| Vane anemometer | Air velocity; some models calculate volume flow. | At air inlets and outlets, including hood faces. | Range and accuracy depend on the model. |
| Thermal anemometer | Air velocity using a thermal probe. | At airflow measurement points, including hoods and ducts. | Range and accuracy depend on the model. |
| Pitot tube and manometer | Static and total pressure, used to work out air velocity in a duct. | At duct test points in a straight section, well downstream of bends (HSG258 paragraph 359). | Testo gives a 150 mm minimum immersion depth for its 0635 2043 tube. |
| Manometer | Static or differential pressure. | At marked test points, hoods and filters. | HSG258 paragraph 295 names inclined, aneroid and micro manometers. |
| Smoke | Air movement and the path of a visible cloud. | Around hoods and processes. | Some tubes produce an acidic mist. Smoke generators can leave residues and are usually unsuitable where smoke detectors are fitted, unless these can be isolated. |
| Dust lamp | Dust or mist illuminated by a strong beam. | Around a running process and hood. | HSG258 says a tripod is essential. |
| Tachometer and power meter | Fan or motor speed and electrical power. | At the fan and motor. | HSG258 identifies a tachometer for a belt-driven fan shaft. |
Where measurements are taken
HSG258 paragraphs 352 to 364 describe measurements for different system parts. The right measurements depend on the system.
Contaminated air Cleaned air
| Part | What HSG258 says to measure | Instrument |
|---|---|---|
| Hood | Static pressure inside a full enclosure (353); face velocity at booths and hoods (354 to 356); hood static pressure and any airflow monitor reading (357). | Anemometer and manometer |
| Ducting | Velocity in a straight section well downstream of bends (paragraph 359). | Pitot tube and manometer or anemometer |
| Air cleaner | Static pressure across the filter; shake down fabric filters with a shake-down device first. Check fitted gauges (paragraphs 361 and 362). | Manometer |
| Air mover | Fan inlet static pressure and volume flow; fan shaft speed for a belt-driven fan (paragraph 360). | Manometer, airflow instrument and tachometer |
| Discharge | The measurement list in paragraphs 352 to 364 names none. Stage 1 examines all parts externally for damage and wear (paragraph 338). | External visual examination |
Airflow indicators on hoods
HSG258 paragraph 228 says users of LEV, particularly the operators at hoods, must be able to tell that hood airflow is still adequate. Paragraph 229 gives a manometer on the hood duct and a pressure switch alarm as examples of airflow indicators.
Paragraph 230 describes electronic manometers with a pressure transducer, mechanical diaphragm manometers and liquid-in-glass manometers. They show static pressure.
Mechanical and liquid manometers need no power and are safe in flammable atmospheres. Liquid manometers are cheap and precise, but bubbles may form or liquid evaporate.
Alarms can fail without warning. HSG258 paragraph 231 says it is good practice for the user manual to state how often to test them.
The HSG258 glossary says that in the past, adequate fitting of manometers has been rare. The LEV guide linked under Where to go next explains what an indicator tells users.
Example equipment models
These examples were found on makers' own pages on 16 November 2026. LevHQ has no link with any maker and does not recommend one. Figures differ between models, so check the current maker page.
| Model | Type | What the maker says | Range and accuracy the maker prints | Maker page |
|---|---|---|---|---|
| Testo 417 | 100 mm vane anemometer | Measures airflow, volume flow and temperature at air inlets and outlets. | 0.3 to 20 m/s; accuracy ±(0.1 m/s + 1.5 % of the reading). | Testo 417 |
| Testo 425 | Hot wire anemometer | A thermal anemometer. | 0.01 to 30 m/s; accuracy ±(0.03 m/s + 4.0 % of the reading) (0.01 to +20 m/s). | Testo 425 |
| Testo 440 dP | Multi-function meter | Built-in differential pressure sensor for Pitot tube and filter measurements. Testo says probes are required and ordered separately. | Differential pressure: 0 to +150 hPa; accuracy ±0.05 hPa (0 to 1.00 hPa), ±(0.2 hPa + 1.5 % of the reading) (1.01 to +150 hPa). | Testo 440 dP |
| Testo 0635 2043 | 360 mm straight Pitot tube | For dust-laden duct flow and higher velocities. Factor 0.67; diameter 8 mm; minimum immersion depth 150 mm. | 1 to 30 m/s. | Testo Pitot tube |
| Testo 510 set | Differential pressure meter | Works with an optional Pitot tube in ducts. | 0 to 100 hPa; accuracy ±0.03 hPa (0 to 0.30 hPa), ±0.05 hPa (0.31 to 1.00 hPa), ±(0.1 hPa + 1.5 % of the reading) (1.01 to 100 hPa). | Testo 510 set |
| Clulite DL4 | Dust lamp | 1 million candle power; beam range up to 1000 m; 2.25 to 5 hours on high and low. | None printed. | Clulite DL4 |
| Concept Flow Check | Handheld smoke generator | For small air movements; smoke for up to 20 minutes on one charge. | None printed. | Concept Flow Check |
| Dräger Air Flow Tester | Smoke tubes and rubber ball | A rubber ball pumps air through tubes containing smoking sulfuric acid, producing white smoke. | None printed. | Dräger Air Flow Tester |
Anemometer calibration and certificates
HSG258 paragraph 295 says measuring instruments should be calibrated. It gives no calibration interval. BOHS P601 also teaches the need for calibration.
Ask to see the certificate and check its date. UKAS publication LAB 5 covers certificates from UKAS accredited calibration laboratories. Its section 3.2 says a certificate needs to include the measurement uncertainty, a statement of conformance with an identified specification, or both.
Under LAB 5 section 3.7, a calibration due date is reported at the customer's request. A due date is not automatically included.
Equipment in flammable atmospheres
HSG258 paragraph 295 says to use intrinsically safe instruments where flammable atmospheres may occur. Paragraph 230 describes mechanical and liquid manometers as safe in flammable atmospheres and requiring no power.
HSG258 paragraph 293 says smoke pellets are inappropriate near flammable substances.
Equipment and your report
HSG258 paragraph 349 says the record of each thorough examination and test should normally state the methods used to judge performance, such as visual checks, smoke tests, airflow and pressure measurements, a dust lamp, air sampling and filter tests.
Paragraph 294 says quantitative measurements can be reproduced and used for comparison. They do not directly prove control. The report guide below explains the results.
Questions to ask your tester
Use these questions before or after the visit.
Tick what your tester has confirmed.
Where to go next
These pages cover the visit, the report and choosing a tester.
| Topic | Read next |
|---|---|
| The test visit | What happens during an LEV test |
| Methods and results | Understanding your LEV report |
| Using hood indicators | Airflow indicators |
| Tester competence | LEV tester qualifications |
| Workplace checks | LEV inspection checklist |
| Find a tester | LEV testing companies |
Check what you know
3 quick questions from this guide. Nothing you choose is saved or sent.
-
Show the answer
Pressure. A manometer indicates pressure.
-
Show the answer
Dust or mist. A strong beam illuminates dust or mist.
-
Show the answer
No interval. Paragraph 295 says instruments should be calibrated but gives no interval.
Questions duty holders ask
What is an airflow indicator on LEV?
It helps users tell whether hood airflow is adequate. HSG258 describes manometers and pressure switch alarms as examples.
How often should an anemometer be calibrated?
HSG258 says measuring instruments should be calibrated but gives no interval. Ask your tester for the certificate and check its date and uncertainty or conformance statement.
What is the difference between a vane and a thermal anemometer?
A vane anemometer measures air speed with a vane: the Testo 417 has a 100 mm vane and reads 0.3 to 20 m/s. A thermal anemometer uses a thermal probe, such as the hot wire on the Testo 425, which reads from 0.01 m/s. BOHS P601 teaches both types.
What does a Pitot tube measure?
A Pitot tube measures static and total pressure. Used with a manometer, it can help determine air velocity in a duct.
Do I need my own LEV test equipment?
Not for the thorough examination. HSG258 paragraph 337 says LEV examiners must have the appropriate equipment, such as Pitot tubes, a smoke generator, a dust lamp and an anemometer. Paragraph 228 says operators must be able to tell that hood airflow is still adequate, so the designer should specify monitors such as manometers or other airflow indicators.
Is your next test due?
Put in the date of the last test and get the deadline, with a reminder if you want one.
LEV test due date calculatorUse the directory to find an LEV tester near you.
Find LEV testing companies
Browse LEV testing companies across the UK, or choose a region.
- LEV testing in East Midlands
- LEV testing in East of England
- LEV testing in London
- LEV testing in North East
- LEV testing in North West
- LEV testing in Northern Ireland
- LEV testing in Scotland
- LEV testing in South East
- LEV testing in South West
- LEV testing in Wales
- LEV testing in West Midlands
- LEV testing in Yorkshire and the Humber
Sources
How this guide was made: LevHQ wrote this guide from the sources listed below and checked it on 16 November 2026. AI tools helped draft and check the text.
- HSE: HSG258, third edition, 2017 (PDF), opened 16 November 2026
- HSE: HSG258 book page, opened 16 November 2026
- BOHS: P601 qualification, opened 16 November 2026
- BOHS: P601 qualification specification, opened 16 November 2026
- UKAS: LAB 5, Reporting calibration results, edition 5, January 2025, opened 16 November 2026
- Testo: 417, opened 16 November 2026
- Testo: 425, opened 16 November 2026
- Testo: 440 dP, opened 16 November 2026
- Testo: straight Pitot tube 360 mm, opened 16 November 2026
- Testo: 510 set, opened 16 November 2026
- Clulite: DL4 dust lamp, opened 16 November 2026
- Concept: Flow Check, opened 16 November 2026
- Dräger: Air Flow Tester, opened 16 November 2026