LEV testing directory and reports for the UK

The essentials

What is LEV testing?

LEV testing is a thorough examination and test of local exhaust ventilation, carried out by a competent person at least every 14 months. It checks that the extraction still pulls dust, fume and vapour away from the people working beside it. This guide explains what the test is, why the law asks for it, what the examiner checks and what happens if a system fails.

First published 22 September 2026. Checked 6 November 2026.

Overhead extraction ducts connect workshop hoods to a fan housing and filter unit.
months, the longest gap between tests for most systems
14
stages in an HSG258 test
3
minimum time to keep the record
5 years
processes with a shorter testing limit
4

What LEV testing is

LEV testing is the everyday name for a thorough examination and test, often shortened to TExT. It is a measured check, not a general service. The examiner checks that the extraction still performs as it was designed to, and that it still helps keep exposure to dust, fume and vapour under control.

HSG258, the HSE guide to LEV, splits the work into three stages. Stage one is a visual and structural check for damage, wear, filters, alarms and working indicators. Stage two reviews technical performance with smoke tests, dust lamp checks and measurements of airflow and pressure. Stage three judges whether the system is controlling exposure in practice, including how operators use it.

You get a written report at the end. It should say whether the system passed, explain any faults and give a prioritised plan for putting them right.

What LEV is

Local exhaust ventilation (LEV) removes contaminated air at or near the point where a work process creates it. That may be dust from sanding, fume from welding or vapour from a solvent process. HSG258 calls these airborne contaminants. Removing them at the source helps stop them reaching the air people breathe.

A simple system has a hood at the process, ducting, a fan or other air mover, an air cleaner and a discharge point. They only work as a set. The guide to local exhaust ventilation, linked under Where to go next, covers the hood types and how the parts fit together.

Why LEV testing matters

HSG258 says thousands of British workers get occupational lung diseases, such as occupational asthma and chronic obstructive pulmonary disease, each year. People develop them by breathing in too much dust, fume or other airborne contaminant at work, often because the control measures do not work well enough. Most industries are affected, including woodworking, welding, paint-spraying, stonemasonry, engineering and foundry work.

A running fan does not prove a hood is catching anything. That is why the law asks for a proper examination and test, not a glance.

Who has to arrange it

The employer does. Under COSHH (the Control of Substances Hazardous to Health Regulations 2002), Regulation 9 says the employer must make sure thorough examination and testing of LEV plant is carried out at least once every 14 months. Northern Ireland has its own COSHH regulations, made in 2003, with the same 14-month limit. Plant used with four processes in Schedule 4 has a shorter limit:

  • Blasting carried out in, or incidental to, the cleaning of metal castings in connection with their manufacture: 1 month.
  • Dry grinding, abrading or polishing of metal articles (not gold, platinum or iridium) using mechanical power, in a room for more than 12 hours in a week: 6 months.
  • Processes that give off dust or fume while non-ferrous metal castings are made: 6 months.
  • Jute cloth manufacture: 1 month.

What the employer must do

The employer acts on the findings and keeps the record for at least five years.

Give the examiner what you have on the intended performance of the system, such as the commissioning report, user manual, logbook and last report. If none exists, the examiner may need to set a benchmark first. HSG258 says that extra work, and its cost, has to be agreed between you and the examiner.

How the test is carried out

HSG258 paragraph 337 states: "LEV examiners must have the appropriate equipment such as Pitot tubes, a smoke generator, a dust lamp, an anemometer and, sometimes, equipment for air sampling." The examiner picks the methods that suit your installation. For the stage two performance review, HSG258 lists checks such as these, as appropriate:

Choose a check to see what it looks for.

  1. Smoke test

    Smoke challenge tests with the process running, to look for smoke leaking out or reaching the breathing zone.

  2. Dust lamp

    Dust lamp tests with the process running, to look for dust or mist escaping.

  3. Airflow speed

    Airflow velocity at hood faces, branch ducts and the main duct.

  4. Static pressure

    Static pressure at marked test points, including across the air cleaner and fan.

  5. Fan checks

    Fan speed, motor speed and the direction the fan turns.

  6. Alarm test

    A test of the alarms by simulating a failure.

A gloved hand holds a digital manometer connected by a tube to a duct test point.

What the main measurements mean

The drawing and table show where each main measurement is taken and what it tells you.

A simple system drawn from the source to the fan. Static pressure is read at several marked test points, two of them shown here.
The main measurements, where each is taken and what it tells you
MeasurementWhere it is takenWhat it tells you
Face velocityAt the open front of a hood. On a larger hood, at several points across the face.The average speed of the air entering the hood, in metres per second. Readings should not vary excessively.
Static pressureAt marked test points, such as the hood, across the air cleaner and at the fan inlet.The difference between the air pressure inside the system and outside it, measured with something like a manometer.
Capture velocityAt the source of the contaminant, at a stated distance from the hood.The speed needed to overcome the movement of the cloud and draw it into the hood. It only means something at that stated distance.

What the examiner compares it with

The examiner compares the results with the design specification in the system documents, such as the user manual. A reading only means something against what the system was meant to achieve.

Tell staff the visit is happening. The examiner should warn employees before smoke tests, and may need smoke alarms turned off while they run.

Testing is not the same as routine checks

HSG258 treats these as two jobs. Routine checks, daily, weekly and monthly, keep the system running properly. A trained employee can do them, and the logbook should set out how often and what to look at. The thorough examination and test is the statutory check, made by a competent person who can judge the system objectively.

Between tests, paragraph 106 names an anemometer, dust lamp or smoke tracer as ways to check with the process running. The simplest way is probably an airflow indicator that shows the operator the hood is working. These checks help, but they do not replace the examination.

What happens if a system fails

HSE recommends a red "Failed" label on any hood or system that has failed, so supervisors and operators are warned directly. It should come with a short written report saying what is wrong and listing practical remedial actions.

The employer then has the hood or system repaired. A competent person has to check that it is effective and controls exposure, and only then can the label come off. Defects should be put right as soon as possible, or within the time the examiner sets, and the repair and retest should be planned and scheduled.

How often a test is needed

For most systems the gap between tests must be no more than 14 months. Test sooner where wear is likely to cut effectiveness between visits. There is no specific legal requirement to fit a test label, though HSE recommends one so operators can see the status. Use the LevHQ LEV test due date calculator for systems on the general 14-month interval.

Who can carry out the test

The examiner must be competent. That can be a contractor you hire or a competent member of your own staff. HSE describes competence as a mix of knowledge, skills and experience.

Ask what qualifications and experience they have, and which types of LEV system they have worked on. A competent supplier should be able to give references. LevHQ lists the qualifications each company says it holds but does not verify them, so check the evidence yourself before you appoint anyone.

What you should receive

HSG258 says the record of each test should normally include these details, among others:

Tick each item your last report included.

Where to go next

This guide is the overview. Each of these goes into one question properly.

LevHQ guides and tools for the next step
If you want to knowGo to
How often your test is dueHow often is LEV testing required?
Your next test dateLEV test due date calculator
What the law saysLEV testing regulations
What the visit involves, step by stepWhat happens during an LEV test?
How to read the reportYour LEV test report and certificate explained
What LEV is and how the parts fit togetherWhat is local exhaust ventilation?
What the HSE guide saysHSG258 explained
What qualifications examiners holdLEV tester qualifications
What testing costsLEV testing cost
How to pick a companyHow to choose an LEV testing company
Companies that test LEV near youLEV testing companies in the UK

Check what you know

4 quick questions from this guide. Nothing you choose is saved or sent.

  1. Who must make sure LEV is thoroughly examined and tested?
    Show the answer

    The employer. COSHH regulation 9 puts the duty on the employer. The examiner carries out the test, but the employer has to make sure it happens.

  2. Which HSG258 stage judges whether the system controls exposure in practice?
    Show the answer

    Stage three. HSG258 paragraph 343 says stage three draws on the visual examination, observation of the process and how operators use the LEV, challenge tests and measurements.

  3. A hood has failed its test. What does HSE recommend?
    Show the answer

    A red "Failed" label and a short written report. HSE recommends a red "Failed" label with a short report on what is wrong and the practical remedial actions. The label stays until a competent person confirms the repair works.

  4. How long should the employer keep the record of a test?
    Show the answer

    At least five years. COSHH regulation 9(4) says the record must stay available for at least five years.

Questions duty holders ask

What does LEV stand for?

LEV stands for local exhaust ventilation. It removes contaminated air at or near the place where dust, fume or vapour is created.

What does LEV testing mean?

It means thoroughly examining and testing local exhaust ventilation, often called an LEV test, to check that it still performs as intended and helps control exposure. The examiner looks at the equipment, measures how it performs and judges whether it is controlling exposure. The written findings should explain any defects and the action needed.

Does a training course make someone competent?

No, not on its own. HSE says competence comes from knowledge, skills and experience together, so ask about the work someone has actually done as well as their certificates.

Does every tested LEV system need a label?

The law does not say you must fit one. HSE still recommends labels, since they show operators and supervisors the test status at a glance. The written report is the record that counts.

Is your next test due?

Put in the date of the last test and get the deadline, with a reminder if you want one.

LEV test due date calculator

Use the directory to find an LEV tester near you.

Find LEV testing companies

Browse LEV testing companies across the UK, or choose a region.